Flooded and VRLA lead acid batteries
Lead acid batteries remain the most common choice for standby power in UPS systems, telecom, substations and industrial DC systems. They come in two main forms:
- Flooded (vented) lead acid: usually 2 V cells with liquid electrolyte, common in utilities and large industrial installations.
- VRLA (valve-regulated lead acid): sealed AGM or gel batteries, available as 2 V cells or 12 V monoblocs, widely used in UPS and telecom.
VRLA batteries are often called "maintenance-free", but they cannot be topped up or inspected internally, which makes electrical monitoring even more important.
How lead acid batteries deteriorate
Common ageing and failure mechanisms include grid corrosion, sulphation, loss of electrolyte (dry-out in VRLA), and loose or corroded inter-cell connections. High temperature accelerates most of these processes. Many of them show up as a gradual rise in internal resistance and a drift in individual cell voltage long before the battery fails a discharge.
Because cells in a string age unevenly, one weak cell can limit the whole string. This is the weakest-battery effect explained in our introduction to battery monitoring.
Parameters to monitor on lead acid batteries
| Parameter | Why it matters |
|---|---|
| Cell / block voltage | Reveals over- or under-charging and cells drifting away from the string average. |
| Cell temperature | High temperature shortens life; hot cells can indicate a fault or thermal risk. |
| Internal resistance | Rises with ageing, dry-out and connection problems; the best early indicator. |
| String voltage & current | Confirms float charging and records charge / discharge events. |
| Ripple voltage | Excess AC ripple from chargers or UPS heats batteries and shortens life. |
| SOC / SOH | Summarises available charge and overall battery health. |
The Erfolgix 7000S measures all of these. It works as a gateway BMS for lead acid 12V batteries as well as 2 V cells: the cell sensor for 12 volt battery BS-12V fits each 12 V monobloc, BS-2V sensors fit 2 V cells, and balancing is available on supported sensors. At string level, the String Current Detect Module – AM (with a Hall sensor from 50 A to 800 A) and the String Voltage Detect Module – UM measure current and voltage, while a 10 inch touch panel HMI configured with BMS-Gate shows every cell on site.
| Parameter | Erfolgix 7000S (typical datasheet values) |
|---|---|
| Cell voltage | BS-2V: 1.6 V to 2.6 V (±0.2%) · BS-12V: 7.5 V to 15.6 V (±0.2%) |
| Cell temperature | −20 °C to +85 °C (±1.0 °C) |
| Internal resistance | 0.1 mΩ to 100 mΩ (repeatability error 1.0% + 25 µΩ) |
| String voltage | UM string sensor: 8 to 1000 VDC (±0.5%) |
| String current | AM string sensor: 1 Hall sensor −1000 to 1000 A; 2 Hall sensors −2000 to 2000 A (±2.0%) |
| Calculated values | SOC, SOH, charge / discharge status |
| Data logging | 8 GB SD card, 12 months, export JPG, PDF, XLS |
Setting alarm limits
Good alarm settings start from the battery manufacturer's data: float voltage window, maximum operating temperature and the baseline internal resistance of new cells. Typical practice is to:
- Set upper and lower cell voltage limits around the recommended float voltage.
- Set a temperature alarm below the manufacturer's maximum, so cooling issues are flagged early.
- Record a resistance baseline after commissioning and alarm on a percentage increase from that baseline.
- Alarm on low SOC so the team knows when the bank has been discharged.
The 7000S provides upper and lower limit alarms for cell voltage, temperature, internal impedance and SOC, with notification by voice, SMS, e-mail and sound-light.
Monitoring and maintenance together
Continuous monitoring does not replace periodic capacity testing, visual inspection or manufacturer instructions. It makes them more targeted: instead of replacing a whole string on age alone, teams can replace the individual blocks that trend data shows are failing, and schedule capacity tests where the data raises questions. Historical records exported as PDF or XLS also support audits and warranty discussions.