Cell-level battery monitoring: see every battery, not just the string
In a series string, the weakest battery sets the limit. The 7000S measures each cell or block individually so a weak unit is found early, before it costs you backup time.
Cell-level measurement
Voltage, temperature and internal impedance (ohmic value) for every BS - 2V, BS - 12V and BS - 1.2V battery, with a balancing function on supported sensors.
String-level insight
String voltage and current, SOC and SOH calculation, and charge or discharge status for each battery string.
Alarms that act
Upper and lower limit alarms for cell voltage, temperature, internal impedance and SOC, with voice, SMS, e-mail and sound-light routing.
7000S system components: cell sensors, string sensors, gateway and HMI

Cell Sensor BS-12V / BS-2V
Cell sensor for 12 volt battery (BS-12V) and for 2 volt cells (BS-2V), one sensor per battery block.
- Voltage, temperature, impedance
- Balancing function

String Sensors AM & UM
String Current Detect Module – AM and String Voltage Detect Module – UM, with Hall sensor options.
- Each connects 60–70 cell sensors
- SOC, SOH, charge status

7000S Gateway (BMS-Gate)
Gateway BMS for lead acid 12V batteries and 2V cells: monitor control gateway with built-in web server.
- Ripple voltage, discharge graphs

10-Inch Touch Panel HMI
10 inch touch panel HMI configured with BMS-Gate to monitor battery parameters in real time on site.
- Cell-by-cell bar view
- Instant exception visibility
System at a glance
Erfolgix 7000S components: gateway, HMI, AM / UM modules, Hall sensors and BS-12V cell sensors
The 7000S is a complete gateway BMS for lead acid 12V batteries, 2V cells and nickel cadmium banks. Each component below appears in the order information.
| Component | Order code | Role in the system |
|---|---|---|
| Gateway BMS (BMS-Gate) | Gateway | Monitor control gateway with web view: collects data from all string and cell sensors, raises alarms and connects to UPS, SCADA and the network. |
| 10 inch touch panel HMI | HMI | Touch panel configured with BMS-Gate to show battery parameters in real time at the battery room. |
| String Current Detect Module – AM | AM | Measures string charge and discharge current through a Hall sensor. |
| String Voltage Detect Module – UM | UM | Measures total string voltage, 8 to 1000 VDC. |
| Hall sensor | Hall Sensor | Current transducer for the AM module, offered as Hall sensor-50A, -200A, -400A and -800A. |
| Cell sensor for 12 volt battery | BS-12V | One-to-one sensor for each 12 V block: voltage, temperature and internal resistance. |
| Cell sensor for 2 volt battery | BS-2V | One-to-one sensor for each 2 V cell: voltage, temperature and internal resistance. |
Full ranges and accuracies are in the technical specifications and the 7000S datasheet.
Battery monitoring software: dashboards that tell you what to do next

Live string status, cell-level comparison and instant visibility of low or high cells.

Voltage trend lines and comparative measurements to track battery-life deterioration over time.
Gateway features: Modbus integration, data logging and export
Built for integration with your UPS, SCADA, building management and network environment, so battery data and alarms reach the right team.
Communication
6 RS485 ports with Modbus and 2 Ethernet ports for data and alarms.
Web access
Built-in web server with web-view pages.
Data and export
8 GB SD card, 12 months logging, export JPG, PDF and XLS.
Reporting
Real-time and historical records with graph analysis.
7000S technical specifications and ordering information
Sensors: functions and records
| Sensor | Description | Monitors & records |
|---|---|---|
| Cell sensor BS-2V Cell / BS-12V Cell | One-to-one cell sensor for 2 V or 12 V batteries, block stethoscope | Cell voltage Cell temperature Cell internal impedance (ohmic value) Balancing function (only for 2V Cell-A & BS 12V Cell-B) |
| String sensor AM | String current: 1 Hall sensor −1000 ~ 1000 A; 2 Hall sensor −2000 A (±2.0%, 15 °C ~ 35 °C) | String voltage, string current SOC & SOH Balancing function extends battery life Batch set address Judge charging and discharging status Each BMS string sensor max. connects 60~70 pc BMS-2V Cell / BMS-12V Cell |
| String sensor UM | String voltage: 8 ~ 1000VDC (±0.5%), battery string stethoscope |
Technical specifications
| Item | Voltage | Temperature | Internal resistance | Power consumption |
|---|---|---|---|---|
| BS-2V Cell | 1.6V to 2.6V (±0.2%) | −20 °C to +85 °C (±1.0 °C) | 0.1 mΩ to 100 mΩ Repeatability error: 1.0% + 25 µΩ Conformity error: 1.5% + 25 µΩ | Running: 170 mW Sleeping: 12 mW |
| BS-12V Cell | 7.5V to 15.6V (±0.2%) | Running: 120 mW Sleeping: 10 mW | ||
| UM | 24VDC (range: 9~32VDC) | Working temperature: −15 °C ~ +55 °C Humidity: 5% ~ 95% RH | Power consumption: <1 W | |
| AM | Power consumption: <0.5 W | |||
1. All specifications are subject to change without prior notice. 2. Data in this datasheet are typical values for reference only, not as a basis for engineering design.
Gateway hardware specifications
| Item | Specification | Item | Specification |
|---|---|---|---|
| CPU | ARM Cortex-A7 528MHz | Memory | 512MB DDR3 |
| ROM | eMMC 4G + SD Card 8G | Communications | 1 RS485, Baud Rate 9600, 19200, 38400bps (optional), Half Duplex |
| Ethernet Port | 2x10/100M Ethernet Port | Power Supply | 2 x AC 220V, Range: AC85~264V/DC120-370V |
| DI | 6 DI, Passive switch input | DO | 6 DO, 250VAC/5A or 30VDC/5A |
| Consumption | < 15W | Power Supply | 2 x AC 220V, Range: AC85~264V/DC120-370V |
| Working Temp | −15 °C ~ +60 °C | Storage Temp | −40 °C ~ +70 °C |
| Humidity | 10-95% RH, No condensation | L*W*H | 430mm x 200mm x 44mm, Standard 1U device (19 inches) |
1. All specifications are subject to change without prior notice. 2. Data in this datasheet are typical values for reference only, not as a basis for engineering design.
Order information
| System structure | Order code | Description |
|---|---|---|
| Communication Layer | Gateway | Monitor Control Gateway with Web View |
| Display | HMI | Monitor battery parameters in real time |
| String Sensor | AM | String current: 1 Hall sensor: −1000 ~ 1000A, 2 Hall sensor: −2000 ~ 2000A (±2.0%, 15 °C ~ 35 °C) |
| String Sensor | UM | String voltage: 8 ~ 1000VDC (±0.5%) |
| String Sensor | Hall Sensor | Hall sensor-50A (Rated input: 50A, Measure range: 0~+100A, Φ20mm) Hall sensor-200A (Rated input: 100A, Measure range: 0~+120A, Φ40mm) Hall sensor-400A (Rated input: 200A, Measure range: 0~+400A, Φ40mm) Hall sensor-800A (Rated input: 400A, Measure range: 0~+800A, Φ40mm) |
| Cell Sensor | BS-2V | 2 volt battery One-One cell sensor |
| Cell Sensor | BS-12V | 12 volt battery One-One cell sensor |
1. All specifications are subject to change without prior notice. 2. Data in this datasheet are typical values for reference only, not as a basis for engineering design.
System architecture

BMS implementation checklist
Battery type & battery bank configurationType of battery, number of strings, cells per string, nominal DC voltage and installation layout
Monitoring parametersVoltage, temperature, internal resistance, ripple, SOC / SOH / SOP
Interfaces & integrationUPS, SCADA / BMS platform, network and alarm routing
System requirements & scopeProtection ratings, communications, power supply, reporting and commissioning scope
Site & environmental conditionsTemperature, humidity, leakage and grounding
Applications
Battery monitoring for UPS, data centres, telecom and utilities
The 7000S protects the backup batteries behind critical operations. Each application has its own guide.
UPS & data centres
Cell-level monitoring of UPS battery strings to protect IT load runtime.
Read the guide →Telecom & substations
Remote monitoring of DC backup batteries at unmanned sites.
Read the guide →Ni-Cd: utilities, oil & gas
Monitoring nickel cadmium banks in substations, plants and railways.
Read the guide →Lead acid & VRLA
Parameters and alarm limits for flooded and VRLA batteries.
Read the guide →UAE, GCC, India & global projects
A specification checklist for projects in the region and worldwide.
Read the guide →New to battery monitoring?
Introduction to battery monitoring systems and the weakest-battery effect.
Start here →Erfolgix supplies the 7000S battery monitoring system and related battery monitoring solutions and products from Dubai to projects in the UAE (Dubai, Abu Dhabi, Sharjah), Saudi Arabia, Qatar, Kuwait, Bahrain, Oman and India, and to customers across the globe. Request a quotation with your battery type and bank configuration.
FAQ
7000S battery monitoring system FAQ
What is included in the Erfolgix 7000S gateway BMS for lead acid 12V batteries?
A typical 7000S system includes the BMS-Gate gateway, a 10 inch touch panel HMI configured with BMS-Gate, the String Current Detect Module – AM with a Hall sensor, the String Voltage Detect Module – UM, and one cell sensor per battery: BS-12V for 12 volt batteries or BS-2V for 2 volt cells.
What do the String Current Detect Module – AM and String Voltage Detect Module – UM do?
The AM module measures string current through Hall sensors (1 Hall sensor −1000 to 1000 A; 2 Hall sensors −2000 to 2000 A, ±2.0%). The UM module measures string voltage from 8 to 1000 VDC (±0.5%). Together they provide string voltage, string current, SOC, SOH and charge / discharge status.
Which Hall sensor sizes are available for the 7000S?
Hall sensors are offered as Hall sensor-50A (measure range 0 to +100 A, Φ20 mm), Hall sensor-200A (0 to +120 A, Φ40 mm), Hall sensor-400A (0 to +400 A, Φ40 mm) and Hall sensor-800A (0 to +800 A, Φ40 mm), as listed in the order information.
What is the cell sensor for 12 volt battery BS-12V?
The BS-12V is a one-to-one cell sensor fitted to each 12 V battery block. It measures block voltage from 7.5 V to 15.6 V (±0.2%), temperature from −20 °C to +85 °C and internal resistance from 0.1 mΩ to 100 mΩ, with a balancing function on the BS 12V Cell-B version.
Which battery types does the Erfolgix 7000S battery monitoring system support?
The Erfolgix 7000S is designed for lead acid (including VRLA) and nickel cadmium (Ni-Cd) battery banks. Cell sensors are available as BS-2V for 2 V cells and BS-12V for 12 V blocks, with one sensor fitted to each cell or block. See the 7000S specifications.
What parameters does the 7000S battery monitoring system measure?
At cell level it measures cell voltage, cell temperature and cell internal impedance (ohmic value). At string level it measures string voltage and string current, calculates SOC and SOH, and works out whether the string is charging or discharging. The gateway also records ripple voltage and discharge graphs.
How accurate are the 7000S cell sensors?
The BS-2V cell sensor measures 1.6 V to 2.6 V (±0.2%) and the BS-12V measures 7.5 V to 15.6 V (±0.2%). Both measure temperature from −20 °C to +85 °C (±1.0 °C) and internal resistance from 0.1 mΩ to 100 mΩ. These are typical datasheet values for reference.
How many cell sensors can one string sensor connect?
Each string sensor connects up to 60–70 cell sensors. The AM string sensor measures string current (1 Hall sensor −1000 to 1000 A; 2 Hall sensors up to −2000 to 2000 A) and the UM string sensor measures string voltage from 8 to 1000 VDC (±0.5%).
How does the 7000S send alarms?
You can set upper and lower limit alarms for cell voltage, temperature, internal impedance and SOC. Alarms can be routed by voice, SMS, e-mail and sound-light, and the gateway has relay outputs (DO) for connection to site alarm systems.
Can the 7000S integrate with UPS, SCADA or a building management system?
Yes. The gateway communicates over RS485 with Modbus and over Ethernet, and has a built-in web server for browser access. It is designed to integrate with UPS, SCADA and network environments.
How long is battery data stored and can it be exported?
The gateway logs 12 months of data on an 8 GB SD card. Real-time and historical records, trends and graphs can be exported as JPG, PDF or XLS files for reports and maintenance records.
Does Erfolgix supply the 7000S in the UAE, the GCC, India and worldwide?
Yes. Erfolgix is based in Dubai Silicon Oasis and serves customers across the UAE, Saudi Arabia, Qatar, Kuwait, Bahrain, Oman and India, and supplies its battery monitoring solutions and products to all countries worldwide. Contact us for project sizing and a quotation.
More answers in our FAQ.
Planning a battery monitoring project?
Share your battery type and monitoring needs.
Erfolgix 7000S battery monitoring system datasheet
| Document name | Download |
|---|---|
| Erfolgix 7000S Battery Monitoring System: Datasheet (PDF) | Download |